Water air curtain, recess mounting, max. mounting height 5 m, protection class IP21, can be connected to BMS, heating capacity: from 8.6 kW (50/40°C) to 21.0 kW (90/70°C), two rows copper heat exchanger with aluminum plates, air flow: three speeds 2000/2300/2400 m³/h, fan power 340 W, length 1 m, height 297 mm, 2 year WARRANTY
Interested in this product? Contact us:

Arvydas Palivonas

LT, RU, EN
+370 601 74426

Sales representative for Vilnius, Ukmergė, Utena, Kaišiadorys and Varėna regions Get Offer

Andrius Lekarevičius

LT, RU, EN
+370 606 11865

Sales representative for Kaunas, Panevėžys, Šiauliai, Telšiai, Klaipėda, Tauragė, Marijampolė and Alytus districts Get Offer
Click on the Model for technical data, dimensions, accessories
ELiS B-W - recess mounting, max. mounting height 5 m, protection class IP21, can be connected to BMS
ELiS B-W-100 Heating capacity: from 5.0 kW (50/40°C) to 11.9 kW (90/70°C), one row copper heat exchanger with aluminum plates, air flow: three speeds 2200/2500/2600 m³/h, fan power 340 W, length 1 m, height 297 mm, 2 year WARRANTY
ELiS B-W-100
Heating capacity: from 5.0 kW (50/40°C) to 11.9 kW (90/70°C), one row copper heat exchanger with aluminum plates, air flow: three speeds 2200/2500/2600 m³/h, fan power 340 W, length 1 m, height 297 mm, 2 year WARRANTY
ELiS B-W-150 Heating capacity: from 8.7 kW (50/40°C) to 20.5 kW (90/70°C), one row copper heat exchanger with aluminum plates, air flow: three speeds 3200/3500/4000 m³/h, fan power 360 W, length 1.5 m, height 297 mm, 2 year WARRANTY
ELiS B-W-150
Heating capacity: from 8.7 kW (50/40°C) to 20.5 kW (90/70°C), one row copper heat exchanger with aluminum plates, air flow: three speeds 3200/3500/4000 m³/h, fan power 360 W, length 1.5 m, height 297 mm, 2 year WARRANTY
ELiS B-W-200 Heating capacity: from 11.6 kW (50/40°C) to 27.7 kW (90/70°C), one row copper heat exchanger with aluminum plates, air flow: three speeds 4000/4300/5200 m³/h, fan power 380 W, length 2 m, height 297 mm, 2 year WARRANTY
ELiS B-W-200
Heating capacity: from 11.6 kW (50/40°C) to 27.7 kW (90/70°C), one row copper heat exchanger with aluminum plates, air flow: three speeds 4000/4300/5200 m³/h, fan power 380 W, length 2 m, height 297 mm, 2 year WARRANTY
ELiS B-W-100 2R Heating capacity: from 8.6 kW (50/40°C) to 21.0 kW (90/70°C), two rows copper heat exchanger with aluminum plates, air flow: three speeds 2000/2300/2400 m³/h, fan power 340 W, length 1 m, height 297 mm, 2 year WARRANTY
ELiS B-W-100 2R
Heating capacity: from 8.6 kW (50/40°C) to 21.0 kW (90/70°C), two rows copper heat exchanger with aluminum plates, air flow: three speeds 2000/2300/2400 m³/h, fan power 340 W, length 1 m, height 297 mm, 2 year WARRANTY
ELiS B-W-150 2R Heating capacity: from 15.2 kW (50/40°C) to 36.7 kW (90/70°C), two rows copper heat exchanger with aluminum plates, air flow: three speeds 3000/3200/3800 m³/h, fan power 360 W, length 1.5 m, height 297 mm, 2 year WARRANTY
ELiS B-W-150 2R
Heating capacity: from 15.2 kW (50/40°C) to 36.7 kW (90/70°C), two rows copper heat exchanger with aluminum plates, air flow: three speeds 3000/3200/3800 m³/h, fan power 360 W, length 1.5 m, height 297 mm, 2 year WARRANTY
ELiS B-W-200 2R Heating capacity: from 20.4 kW (50/40°C) to 49.9 kW (90/70°C), two rows copper heat exchanger with aluminum plates, air flow: three speeds 3800/4100/5000 m³/h, fan power 380 W, length 2 m, height 297 mm, 2 year WARRANTY
ELiS B-W-200 2R
Heating capacity: from 20.4 kW (50/40°C) to 49.9 kW (90/70°C), two rows copper heat exchanger with aluminum plates, air flow: three speeds 3800/4100/5000 m³/h, fan power 380 W, length 2 m, height 297 mm, 2 year WARRANTY

Dimensions

Model: ELiS B-W-100 2R

Heating capacity tables

ELiS B-W-100 2R airflow on 3 speed = 2400 m³/h
Tp1
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
 
0
5
10
15
20
Tw1/Tw2 = 90/70°C
24,5
1080
1,8
30,0
22,8
1004
1,6
33,0
21,0
928
1,4
36,0
19,3
853
1,2
38,5
17,6
776
1,0
41,5
 
0
5
10
15
20
Tw1/Tw2 = 80/60°C
20,5
900
1,3
25,5
18,8
824
1,1
28,0
17,0
747
1,0
31,0
15,3
670
0,8
33,5
13,5
592
0,6
36,5
 
0
5
10
15
20
Tw1/Tw2 = 70/50°C
16,4
716
0,9
20,0
14,6
639
0,7
23,0
12,8
560
0,6
25,5
11,0
479
0,4
28,5
9,0
395
0,3
31,0
 
0
5
10
15
20
Tw1/Tw2 = 70/40°C
10,1
293
0,2
12,5
5,6
164
0,1
12,0
4,9
143
0,1
16,0
4,2
122
0,0
20,0
3,5
102
0,0
24,0
 
0
5
10
15
20
Tw1/Tw2 = 60/40°C
12,0
521
0,5
15,0
10,0
436
0,4
17,5
7,8
341
0,2
19,5
4,0
174
0,1
20,0
3,3
142
0,1
24,0
 
0
5
10
15
20
Tw1/Tw2 = 50/40°C
13,2
1148
2,3
16,5
11,4
994
1,7
19,0
9,6
838
1,3
22,0
7,8
679
0,9
24,5
5,9
512
0,5
27,0
ELiS B-W-100 2R airflow on 2 speed = 2300 m³/h
Tp1
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
 
0
5
10
15
20
Tw1/Tw2 = 90/70°C
23,9
1053
1,7
30,5
22,2
980
1,5
33,5
20,5
906
1,3
36,0
18,8
832
1,1
39,0
17,2
757
1,0
41,5
 
0
5
10
15
20
Tw1/Tw2 = 80/60°C
20,0
878
1,3
25,5
18,3
803
1,1
28,5
16,6
729
0,9
31,0
14,9
654
0,7
34,0
13,1
578
0,6
36,5
 
0
5
10
15
20
Tw1/Tw2 = 70/50°C
16,0
699
0,9
20,5
14,2
623
0,7
23,5
12,5
546
0,6
26,0
10,7
467
0,4
28,5
8,8
384
0,3
31,0
 
0
5
10
15
20
Tw1/Tw2 = 70/40°C
9,7
282
0,2
12,5
5,6
162
0,1
12,0
4,9
141
0,1
16,0
4,2
121
0,0
20,5
3,5
101
0,0
24,5
 
0
5
10
15
20
Tw1/Tw2 = 60/40°C
11,6
508
0,5
15,0
9,7
424
0,4
17,5
7,6
329
0,2
19,5
4,0
173
0,1
20,0
3,2
141
0,1
24,0
 
0
5
10
15
20
Tw1/Tw2 = 50/40°C
12,9
1120
2,2
16,5
11,1
969
1,7
19,5
9,4
817
1,2
22,0
7,6
662
0,8
24,5
5,7
498
0,5
27,0
ELiS B-W-100 2R airflow on 1 speed = 2000 m³/h
Tp1
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
 
0
5
10
15
20
Tw1/Tw2 = 90/70°C
22,0
970
1,5
32,5
20,4
902
1,3
35,0
18,9
834
1,1
38,0
17,4
766
1,0
40,5
15,8
697
0,8
43,0
 
0
5
10
15
20
Tw1/Tw2 = 80/60°C
18,4
808
1,1
27,0
16,8
740
0,9
30,0
15,3
671
0,8
32,5
13,7
601
0,6
35,0
12,1
531
0,5
37,5
 
0
5
10
15
20
Tw1/Tw2 = 70/50°C
14,7
643
0,7
22,0
13,1
573
0,6
24,5
11,5
501
0,5
27,0
9,8
428
0,4
29,5
8,0
350
0,3
31,5
 
0
5
10
15
20
Tw1/Tw2 = 70/40°C
6,1
177
0,1
9,0
5,4
157
0,1
13,0
4,7
137
0,0
17,0
4,0
117
0,0
21,0
3,4
98
0,0
25,0
 
0
5
10
15
20
Tw1/Tw2 = 60/40°C
10,7
464
0,4
16,0
8,8
386
0,3
18,0
6,6
289
0,2
20,0
3,8
167
0,1
20,5
3,1
137
0,1
24,5
 
0
5
10
15
20
Tw1/Tw2 = 50/40°C
11,8
1030
1,9
17,5
10,2
891
1,4
20,0
8,6
751
1,0
22,5
7,0
607
0,7
25,0
5,2
454
0,4
27,5
  • PT - heating capacity
  • Tp1 - air temperature at the unit inlet
  • Tp2 - air temperature at the unit outlet
  • Tw1 - heating medium temperature at the heat exchanger inlet
  • Tw2 - heating medium temperature at the heat exchanger outlet
  • Qw - heating medium flow rate in heat exchanger
  • Δpw - heating medium pressure drop in heat exchanger

If you want to calculate heating capacity at different parameters you can do this at manufacturer website.

ELiS B recessed air curtains
Manuals 2.7 MB
Declarations of conformity 659 KB
Brochures 12.9 MB
Catalogue 1.3 MB
AutoCAD drawings 1.1 MB
BIM objects 5.2 MB
TS controller for equipment with 3-speed fans
Manuals 187 KB
Declarations of conformity 211 KB
T-box controller
Manuals 22.7 MB
Declarations of conformity 643 KB
MODBUS protocol for connection to BMS 1.9 MB
T-box Zone controller
Manuals 7.4 MB
Declarations of conformity 643 KB
MODBUS protocol for connection to BMS 1.7 MB