Fan heater, three speed FLOWAIR axial fan, EPP casing, rotating mounting bracket, one row heat exchanger, 2-25 kW heating capacity, air flow 1700/2800/4250 m³/h, fan power 120/240/330 W, weight 14.9 kg, 3 year WARRANTY
Interested in this product? Contact us:

Arvydas Palivonas

LT, RU, EN
+370 601 74426

Sales representative for Vilnius, Ukmergė, Utena, Kaišiadorys and Varėna regions Get Offer

Andrius Lekarevičius

LT, RU, EN
+370 606 11865

Sales representative for Kaunas, Panevėžys, Šiauliai, Telšiai, Klaipėda, Tauragė, Marijampolė and Alytus districts Get Offer
Model: LEO L1
General data
Heating capacity at 90/70°C water and 0°C air temperature
kW
24,6
Heating capacity at 40/30°C water and 20°C air temperature
kW
1,6
Max. air flow
m³/h
4250
Fan data
Power supply
V/Hz
230/50
Fan type
3-speed AC
IP / Insulation class
54 / F
Fan data at 3rd (max) speed
Air flow
m³/h
4250
Air flow range (measured horizontaly at 0.5 m/s speed limit)
m
24,0
Air flow range (measured verticaly at 0.5 m/s speed limit)
m
8,3
Power consumption
W
330
Current consumption
A
1,4
Acoustic pressure level at a distance of 5 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
64,1
Acoustic power level according to EN ISO 3744:2011
dB(A)
79,2
Fan data at 2nd (mid) speed
Air flow
m³/h
2800
Air flow range (measured horizontaly at 0.5 m/s speed limit)
m
15,0
Air flow range (measured verticaly at 0.5 m/s speed limit)
m
5,6
Power consumption
W
240
Current consumption
A
1,2
Acoustic pressure level at a distance of 5 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
54,5
Acoustic power level according to EN ISO 3744:2011
dB(A)
69,6
Fan data at 1st (min) speed
Air flow
m³/h
1700
Air flow range (measured horizontaly at 0.5 m/s speed limit)
m
9,5
Air flow range (measured verticaly at 0.5 m/s speed limit)
m
3,7
Power consumption
W
120
Current consumption
A
0,6
Acoustic pressure level at a distance of 5 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
42,1
Acoustic power level according to EN ISO 3744:2011
dB(A)
57,2
Installation data
Max. operating temperature
°C
60
Max. heating water temperature
°C
120
Max. operating pressure
MPa
1,6
Hydraulic connection
Ø "
¾
Other data
Heat exchanger
Copper with aluminum plates, one row
Casing
EPP - expanded polypropylene
Color
Grey / graphite (ral 9007)
Dimensions
Width
mm
650
Depth
mm
355
Height
mm
580
Weight
kg
14,9
Weight of unit filled with water
kg
15,9

Dimensions

Model: LEO L1

Heating capacity tables

LEO L1 airflow on 3 speed = 4250 m³/h
Tp1
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
 
0
5
10
15
20
Tw1/Tw2 = 120/90°C
32,3
961
7,0
22,5
30,7
913
6,4
26,5
29,1
865
5,8
30,0
27,5
818
5,2
34,0
25,9
770
4,7
37,5
 
0
5
10
15
20
Tw1/Tw2 = 90/70°C
24,6
1086
9,4
17,0
23,0
1014
8,3
21,0
21,3
941
7,2
25,0
19,7
869
6,3
28,5
18,0
796
5,3
32,5
 
0
5
10
15
20
Tw1/Tw2 = 80/60°C
20,9
917
7,1
14,5
19,2
845
6,1
18,5
17,6
772
5,2
22,0
15,9
699
4,3
26,0
14,2
625
3,5
29,5
 
0
5
10
15
20
Tw1/Tw2 = 70/50°C
17,1
749
5,1
12,0
15,4
676
4,2
15,5
13,8
602
3,4
19,5
12,1
528
2,7
23,5
10,4
453
2,1
27,0
 
0
5
10
15
20
Tw1/Tw2 = 60/40°C
13,3
578
3,3
9,0
11,6
504
2,6
13,0
9,8
429
1,9
17,0
8,1
352
1,4
20,5
6,2
272
0,9
24,5
 
0
5
10
15
20
Tw1/Tw2 = 40/30°C
9,8
845
7,0
7,0
8,0
697
4,9
10,5
6,3
547
3,2
14,5
4,5
391
1,8
18,0
1,6
139
0,3
21,0
LEO L1 airflow on 2 speed = 2800 m³/h
Tp1
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
 
0
5
10
15
20
Tw1/Tw2 = 120/90°C
26,0
773
4,7
27,5
24,7
735
4,3
31,0
23,4
697
3,9
34,5
22,1
659
3,5
38,0
20,8
621
3,2
41,5
 
0
5
10
15
20
Tw1/Tw2 = 90/70°C
19,8
873
6,3
21,0
18,5
815
5,6
24,5
17,2
757
4,9
28,0
15,8
699
4,2
31,5
14,5
641
3,6
35,0
 
0
5
10
15
20
Tw1/Tw2 = 80/60°C
16,8
737
4,8
18,0
15,5
679
4,1
21,5
14,1
621
3,5
25,0
12,8
563
2,9
28,5
11,5
504
2,4
32,0
 
0
5
10
15
20
Tw1/Tw2 = 70/50°C
13,8
602
3,4
14,5
12,4
543
2,9
18,0
11,1
485
2,3
21,5
9,7
425
1,8
25,0
8,3
365
1,4
28,5
 
0
5
10
15
20
Tw1/Tw2 = 60/40°C
10,7
464
2,2
11,5
9,3
405
1,7
15,0
7,9
344
1,3
18,5
6,5
281
0,9
21,5
4,9
214
0,6
25,0
 
0
5
10
15
20
Tw1/Tw2 = 40/30°C
7,8
678
4,7
8,5
6,5
559
3,3
12,0
5,1
437
2,1
15,5
3,6
310
1,2
18,5
1,5
127
0,2
21,5
LEO L1 airflow on 1 speed = 1700 m³/h
Tp1
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
 
0
5
10
15
20
Tw1/Tw2 = 120/90°C
19,7
586
2,9
34,5
18,7
558
2,6
37,5
17,8
529
2,4
40,5
16,8
500
2,1
44,0
15,8
472
1,9
47,0
 
0
5
10
15
20
Tw1/Tw2 = 90/70°C
15,0
661
3,8
26,0
14,0
618
3,4
29,5
13,0
574
2,9
32,5
12,0
530
2,6
35,5
11,0
486
2,2
39,0
 
0
5
10
15
20
Tw1/Tw2 = 80/60°C
12,7
559
2,9
22,0
11,7
515
2,5
25,5
10,7
471
2,1
28,5
9,7
427
1,8
31,5
8,7
382
1,5
35,0
 
0
5
10
15
20
Tw1/Tw2 = 70/50°C
10,4
456
2,1
18,0
9,4
412
1,7
21,5
8,4
367
1,4
24,5
7,4
322
1,1
27,5
6,3
276
0,8
31,0
 
0
5
10
15
20
Tw1/Tw2 = 60/40°C
8,1
351
1,4
14,0
7,0
305
1,1
17,0
5,9
258
0,8
20,5
4,8
209
0,5
23,5
3,5
151
0,3
26,0
 
0
5
10
15
20
Tw1/Tw2 = 40/30°C
5,9
512
2,8
10,5
4,9
421
2,0
13,5
3,8
327
1,3
16,5
2,6
224
0,7
19,5
1,3
111
0,2
22,0
  • PT - heating capacity
  • Tp1 - air temperature at the unit inlet
  • Tp2 - air temperature at the unit outlet
  • Tw1 - heating medium temperature at the heat exchanger inlet
  • Tw2 - heating medium temperature at the heat exchanger outlet
  • Qw - heating medium flow rate in heat exchanger
  • Δpw - heating medium pressure drop in heat exchanger

If you want to calculate heating capacity at different parameters you can do this at manufacturer website.