Electric heat pump, reversible, Air/Air, in the heating mode it takes heat from the Outdoor Air and transfers it to the Indoor Air, in cooling mode it takes heat from the Indoor Air and transfers it to the Outdoor Air, consists of outdoor and indoor unit, OUTDOOR UNIT DATA: nominal heat output 39 kW (A7/A20), COP 4.45 (A7/A20), nominal cooling output 35 kW (A35/A27), EER 4.02 (A35/A27), max. electrical power consumption 12 kW, max. sound power 60.2 dB(A), operating temperature of outside air in heating mode -25/+35°C, operating temperature of outside air in cooling mode +18/+46°C, refrigerant type R32, max. distance to indoor unit 30 m, dimensions 1791x641xH1257 mm, weight 270 kg, INDOOR UNIT DATA: maks. air flow 6000 m³/h, max. sound power 59.6 dB(A), dimensions 1253x825xH1139 mm, weight 110 kg
Interested in this product? Contact us:

Arvydas Palivonas

LT, RU, EN
+370 601 74426

Sales representative for Vilnius, Ukmergė, Utena, Kaišiadorys and Varėna regions Get Offer

Andrius Lekarevičius

LT, RU, EN
+370 606 11865

Sales representative for Kaunas, Panevėžys, Šiauliai, Telšiai, Klaipėda, Tauragė, Marijampolė and Alytus districts Get Offer
Click on the Model for technical data, dimensions, accessories
e-NextPro - reversible, Air/Air, in the heating mode it takes heat from the Outdoor Air and transfers it to the Indoor Air, in cooling mode it takes heat from the Indoor Air and transfers it to the Outdoor Air, consists of outdoor and indoor unit
e-NextPro 40 OUTDOOR UNIT DATA: nominal heat output 39 kW (A7/A20), COP 4.45 (A7/A20), nominal cooling output 35 kW (A35/A27), EER 4.02 (A35/A27), max. electrical power consumption 12 kW, max. sound power 60.2 dB(A), operating temperature of outside air in heating mode -25/+35°C, operating temperature of outside air in cooling mode +18/+46°C, refrigerant type R32, max. distance to indoor unit 30 m, dimensions 1791x641xH1257 mm, weight 270 kg, INDOOR UNIT DATA: maks. air flow 6000 m³/h, max. sound power 59.6 dB(A), dimensions 1253x825xH1139 mm, weight 110 kg
e-NextPro 40
OUTDOOR UNIT DATA: nominal heat output 39 kW (A7/A20), COP 4.45 (A7/A20), nominal cooling output 35 kW (A35/A27), EER 4.02 (A35/A27), max. electrical power consumption 12 kW, max. sound power 60.2 dB(A), operating temperature of outside air in heating mode -25/+35°C, operating temperature of outside air in cooling mode +18/+46°C, refrigerant type R32, max. distance to indoor unit 30 m, dimensions 1791x641xH1257 mm, weight 270 kg, INDOOR UNIT DATA: maks. air flow 6000 m³/h, max. sound power 59.6 dB(A), dimensions 1253x825xH1139 mm, weight 110 kg
Model: e-NextPro 40
General data
Nominal heating output at 7°C outdoor and 20°C indoor air temperature
kW
39
Nominal heating output at -7°C outdoor and 20°C indoor air temperature
kW
32
COP - heating coefficient of performance at 7°C outdoor and 20°C indoor air temperature
4,45
COP - heating coefficient of performance at -7°C outdoor and 20°C indoor air temperature
3,20
Nominal cooling output at 35°C outdoor and 27°C indoor air temperature
kW
35
EER - cooling energy efficiency ratio at 35°C outdoor and 27°C indoor air temperature
4,02
Max. electrical power consumption
kW
12
Compressor system
Type
Scroll inverter vapor injection
Refrigerant type
R32
Refrigerant GWP
675
Refrigerant quantity if distance between outdoor and indoor unit does not exceed 10 m
kg
7,4
Outdoor unit fan data
Max. air flow
m³/h
15000
Max. sound power level
dB(A)
60,2
Fan type
Axial inverter
Nominal diameter
mm Ø
910
Indoor unit fan data
Max. air flow
m³/h
6000
Max. sound power level
dB(A)
59,6
Fan type
Axial inverter BLDC
Nominal diameter
mm Ø
800
Installation data
Power supply
V / Hz / Ph
400 / 50 / 3
Max. electrical power consumption
kW
12
Gas coolant connection diameter
Ø mm (")
22 (7/8)
Liquid coolant connection diameter
Ø mm (")
16 (5/8)
Max. coolant connection length between outdoor and indoor unit
m
30
Operating temperature range in heating mode
°C
-25 / +35
Operating temperature range in cooling mode
°C
+18 / +46
Outdoor unit dimensions
Width
mm
1791
Depth
mm
641
Height
mm
1257
Weight
kg
270
Indoor unit dimensions
Width
mm
1253
Depth
mm
825
Height
mm
1139
Weight
kg
110

Dimensions

Model: e-NextPro 40

Heating full load performance (EN 14511-2) at 20°C room temperature

Room temperature (dry bulb) [°C] 20
Outdoor moduleDeclared output [kW]COP
Outdoor temperature (dry bulb) [°C]Outdoor temperature (wet bulb) [°C]
-25 - 24,00 2,18
-20 - 27,00 2,50
-15 - 32,00 2,70
-10 -11 32,00 2,97
-7 -8 32,00 3,20
2 1 35,00 3,75
7 6 39,00 4,45
12 11 39,00 4,70

Heating full load performance (EN 14511-2) at 15°C room temperature

Room temperature (dry bulb) [°C] 15
Outdoor moduleDeclared output [kW]COP
Outdoor temperature (dry bulb) [°C]Outdoor temperature (wet bulb) [°C]
-25 - - -
-20 - 27,00 2,73
-15 - 32,03 2,94
-10 -11 32,06 3,25
-7 -8 32,19 3,44
2 1 35,03 4,26
7 6 39,53 4,83
12 11 42,23 5,34

Cooling full load performance (EN 14511-2)

Room temperature (dry bulb) [°C] 27
Outdoor moduleDeclared output [kW]EER
Outdoor temperature (dry bulb) [°C]
35 35,00 4,02
e-NextPro electric heat pump Air/Air
Catalogue 410 KB