Gas absorption heat pump, reversible, on heating operation mode takes heat from Air and gives it to Water for heating, on cooling operation mode takes heat from Water for cooling and gives it to Air, maximum outlet water temperature for heating 60°C, heating capacity 37.8 kW (A7/W35), G.U.E. gas utilization efficiency for heating 150% (A7/W35), A+ energy class ErP on 55°C operation, minimum outlet water temperature for cooling 3°C, cooling capacity 16.9 kW (A35/W7), G.U.E. gas utilization efficiency for cooling 67% (A35/W7), gas (G20) consumption 2.67 m³/h, electrical power consumption 0.84 kW, sound pressure level (at 5 m distance) 57.6 dB(A), water connection 1¼", electrical degree of protection IP X5D, weight 380 kg, outside working temperature in heating mode -20°C/+35°C, outside working temperature in cooling mode 0°C/+45°C
Interested in this product? Contact us:

Arvydas Palivonas

LT, RU, EN
+370 601 74426

Sales representative for Vilnius, Ukmergė, Utena, Kaišiadorys and Varėna regions Get Offer

Andrius Lekarevičius

LT, RU, EN
+370 606 11865

Sales representative for Kaunas, Panevėžys, Šiauliai, Telšiai, Klaipėda, Tauragė, Marijampolė and Alytus districts Get Offer
Model: GAHP-AR STANDARD
Heating operation mode data
Energy class (55°C operation)
ErP
A+
G.U.E. gas utilization efficiency at 35°C water and 7°C air temperature
%
150
Heating capacity at 35°C water and 7°C air temperature
kW
37,8
G.U.E. gas utilization efficiency at 50°C water and 7°C air temperature
%
140
Heating capacity at 50°C water and 7°C air temperature
kW
35,3
Nominal water flow rate (ΔT = 10°C)
m³/h
3,04
Nominal water pressure loss (outlet water at 50°C)
kPa
29
Maximum outlet water temperature (ΔT = 10°C)
°C
+60
Minimum / Maximum inlet water temperature
°C
+20 / +50
Operating temperature range
°C
-20 / +35
Operating temperature range with winter kit
°C
-30 / +35
Cooling operation mode data
G.U.E. gas utilization efficiency at 7°C water and 35°C air temperature
%
67
Cooling capacity at 7°C water and 35°C air temperature
kW
16,9
Nominal water flow rate (ΔT = 5°C)
m³/h
2,9
Nominal water pressure loss (outlet water at 7°C)
kPa
31
Minimum outlet water temperature
°C
+3
Minimum / Maximum inlet water temperature
°C
+6 / +45
Operating temperature range
°C
0 / +45
Burner characteristics
Thermal input (actual)
kW
25,2
Natural gas (G20) consumption at 15 °C - 1013 mbar
m³/h
2,67
LPG G30 / G31 consumption at 15 °C - 1013 mbar
kg/h
1,96
Installation data
Power supply
V/Hz
230/50
Nominal electrical power consumption
kW
0,84
Sound pressure at 5 meters distance from unit front side in free field
dB(A)
57,6
IP protection class
X5D
Hydraulic connection
Ø "
F 1 1/4
Gas connection
Ø "
F 3/4
Exhaust air flue diameter
mm Ø
80
Dimensions
Width
mm
850
Depth
mm
1230
Height
mm
1445
Weight
kg
380

Dimensions

Model: GAHP-AR STANDARD