Water air curtain, horizontal and vertical mounting, 3 step fan, protection class IP20, mounting height up to 3.5 m, built in control system (motion sensor, water valve switch, 2 selected fan steps switch), very thin - only 189 mm in height, heating capacity: from 3.2 kW (50/40°C) to 8.2 kW (90/70°C), air flow 770/900/1100 m³/h, fan power 75/90/115 W, sound pressure level 45/50/55 dB(A), length 1 m, weight 16.2 kg, white color, 2 year WARRANTY
Interested in this product? Contact us:

Arvydas Palivonas

LT, RU, EN
+370 601 74426

Sales representative for Vilnius, Ukmergė, Utena, Kaišiadorys and Varėna regions Get Offer

Andrius Lekarevičius

LT, RU, EN
+370 606 11865

Sales representative for Kaunas, Panevėžys, Šiauliai, Telšiai, Klaipėda, Tauragė, Marijampolė and Alytus districts Get Offer
Model: SLIM W-100 WHITE
General data
Heating capacity at 90/70°C water and 10°C air temperature, fan at max speed
kW
8,2
Heating capacity at 50/40°C water and 10°C air temperature, fan at min speed
kW
3,2
Air flow range
m
3,5
Max. air flow
m³/h
1100
Fan data
Steps
3
Fan data at 3rd (max) speed
Air flow
m³/h
1100
Air flow with filter (Coarse 30%)
m³/h
750
Air flow range
m
3,5
Power consumption
W
115
Current consumption
A
0,5
Acoustic pressure level at a distance of 3 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
56
Acoustic pressure level at a distance of 5 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
55
Acoustic power level according to ISO 27327-2
dB(A)
70
Fan data at 2nd (mid) speed
Air flow
m³/h
900
Air flow with filter (Coarse 30%)
m³/h
650
Air flow range
m
2,8
Power consumption
W
90
Current consumption
A
0,4
Acoustic pressure level at a distance of 3 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
51
Acoustic pressure level at a distance of 5 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
50
Acoustic power level according to ISO 27327-2
dB(A)
66
Fan data at 1st (min) speed
Air flow
m³/h
770
Air flow with filter (Coarse 30%)
m³/h
600
Air flow range
m
2,1
Power consumption
W
75
Current consumption
A
0,3
Acoustic pressure level at a distance of 3 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
46
Acoustic pressure level at a distance of 5 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
45
Acoustic power level according to ISO 27327-2
dB(A)
61
Installation data
Power supply
V/Hz
1N ~ 230/50
IP protection class
20
Installation
Horizontal / vertical
Max. heating water temperature
°C
110
Max. operating pressure
MPa
1,6
Hydraulic connection
Ø "
½
Max. mounting height
m
3,5
Other data
Color
White
Dimensions
Length
mm
1000
Depth
mm
399
Height
mm
189
Weight without water
kg
16,2
Weight of unit filled with water
kg
16,8

Dimensions

Model: SLIM W-100 WHITE

Heating capacity tables

SLIM W-100 WHITE airflow on 3 speed = 1100 m³/h
Tp1
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
 
0
5
10
15
20
Tw1/Tw2 = 110/90°C
12,1
537
7,9
32,5
11,5
511
7,2
36,0
10,9
486
6,5
39,0
10,3
460
5,9
42,5
9,7
434
5,3
46,0
 
0
5
10
15
20
Tw1/Tw2 = 90/70°C
9,4
414
5,2
25,5
8,8
388
4,6
28,5
8,2
362
4,1
32,0
7,6
336
3,5
35,5
7,0
309
3,1
38,5
 
0
5
10
15
20
Tw1/Tw2 = 80/60°C
8,1
354
4,0
22,0
7,5
327
3,5
25,0
6,8
301
3,0
28,5
6,2
274
2,5
31,5
5,6
247
2,1
35,0
 
0
5
10
15
20
Tw1/Tw2 = 70/50°C
6,7
293
3,0
18,0
6,1
266
2,5
21,5
5,5
239
2,1
24,5
4,9
212
1,7
28,0
4,2
185
1,3
31,5
 
0
5
10
15
20
Tw1/Tw2 = 60/40°C
5,3
231
2,0
14,5
4,7
204
1,6
17,5
4,1
177
1,3
21,0
3,4
149
0,9
24,0
2,8
120
0,6
27,5
 
0
5
10
15
20
Tw1/Tw2 = 50/40°C
5,2
451
6,8
14,0
4,6
398
5,4
17,5
4,0
344
4,2
20,5
3,3
290
3,1
24,0
2,7
235
2,1
27,0
SLIM W-100 WHITE airflow on 2 speed = 900 m³/h
Tp1
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
 
0
5
10
15
20
Tw1/Tw2 = 110/90°C
10,7
477
6,3
35,5
10,2
454
5,8
38,5
9,7
431
5,3
42,0
9,2
408
4,8
45,0
8,7
385
4,3
48,0
 
0
5
10
15
20
Tw1/Tw2 = 90/70°C
8,3
368
4,2
27,5
7,8
345
3,7
31,0
7,3
322
3,3
34,0
6,8
298
2,9
37,0
6,2
275
2,5
40,0
 
0
5
10
15
20
Tw1/Tw2 = 80/60°C
7,2
314
3,3
23,5
6,6
291
2,8
27,0
6,1
267
2,4
30,0
5,5
244
2,1
33,0
5,0
220
1,7
36,5
 
0
5
10
15
20
Tw1/Tw2 = 70/50°C
5,9
260
2,4
19,5
5,4
236
2,0
22,5
4,9
213
1,7
26,0
4,3
189
1,4
29,0
3,8
164
1,1
32,0
 
0
5
10
15
20
Tw1/Tw2 = 60/40°C
4,7
205
1,7
15,5
4,2
181
1,3
19,0
3,6
157
1,0
22,0
3,0
132
0,8
25,0
2,4
106
0,5
28,0
 
0
5
10
15
20
Tw1/Tw2 = 50/40°C
4,6
400
5,5
15,5
4,1
353
4,4
18,5
3,5
305
3,4
21,5
3,0
257
2,5
24,5
2,4
208
1,7
28,0
SLIM W-100 WHITE airflow on 1 speed = 770 m³/h
Tp1
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
 
0
5
10
15
20
Tw1/Tw2 = 110/90°C
9,8
435
5,4
37,5
9,3
414
4,9
40,5
8,8
393
4,5
44,0
8,4
372
4,0
47,0
7,9
351
3,6
50,0
 
0
5
10
15
20
Tw1/Tw2 = 90/70°C
7,6
335
3,5
29,5
7,1
314
3,2
32,5
6,6
293
2,8
35,5
6,2
272
2,4
38,5
5,7
250
2,1
41,5
 
0
5
10
15
20
Tw1/Tw2 = 80/60°C
6,5
286
2,8
25,0
6,0
265
2,4
28,0
5,5
244
2,1
31,5
5,1
222
1,8
34,5
4,6
200
1,5
37,5
 
0
5
10
15
20
Tw1/Tw2 = 70/50°C
5,4
237
2,0
21,0
4,9
215
1,7
24,0
4,4
194
1,4
27,0
3,9
172
1,2
30,0
3,4
150
0,9
33,0
 
0
5
10
15
20
Tw1/Tw2 = 60/40°C
4,3
187
1,4
16,5
3,8
165
1,1
19,5
3,3
143
0,9
22,5
2,8
120
0,6
25,5
2,2
95
0,4
28,5
 
0
5
10
15
20
Tw1/Tw2 = 50/40°C
4,2
365
4,7
16,0
3,7
322
3,7
19,5
3,2
278
2,9
22,5
2,7
234
2,1
25,5
2,2
189
1,5
28,5
  • PT - heating capacity
  • Tp1 - air temperature at the unit inlet
  • Tp2 - air temperature at the unit outlet
  • Tw1 - heating medium temperature at the heat exchanger inlet
  • Tw2 - heating medium temperature at the heat exchanger outlet
  • Qw - heating medium flow rate in heat exchanger
  • Δpw - heating medium pressure drop in heat exchanger

If you want to calculate heating capacity at different parameters you can do this at manufacturer website.