Water air curtain, horizontal and vertical mounting, 3 step fan, protection class IP20, mounting height up to 3.5 m, built in control system (motion sensor, water valve switch, 2 selected fan steps switch), very thin - only 189 mm in height, heating capacity: from 8.6 kW (50/40°C) to 24.2 kW (90/70°C), air flow 1150/1310/1830 m³/h, fan power 78/93/146 W, sound pressure level 44/48/56 dB(A), length 1.5 m, weight 22,7 kg, white color, 2 year WARRANTY
Interested in this product? Contact us:

Arvydas Palivonas

LT, RU, EN
+370 601 74426

Sales representative for Vilnius, Ukmergė, Utena, Kaišiadorys and Varėna regions Get Offer

Andrius Lekarevičius

LT, RU, EN
+370 606 11865

Sales representative for Kaunas, Panevėžys, Šiauliai, Telšiai, Klaipėda, Tauragė, Marijampolė and Alytus districts Get Offer
Model: SLIM W-150 2R WHITE
General data
Heating capacity at 90/70°C water and 10°C air temperature, fan at max speed
kW
24,2
Heating capacity at 50/40°C water and 10°C air temperature, fan at min speed
kW
8,6
Air flow range
m
3,5
Max. air flow
m³/h
1830
Fan data
Steps
3
Fan data at 3rd (max) speed
Air flow
m³/h
1830
Air flow with filter (Coarse 30%)
m³/h
1050
Air flow range
m
3,5
Power consumption
W
146
Current consumption
A
0,65
Acoustic pressure level at a distance of 3 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
57
Acoustic pressure level at a distance of 5 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
56
Acoustic power level according to ISO 27327-2
dB(A)
72
Fan data at 2nd (mid) speed
Air flow
m³/h
1310
Air flow with filter (Coarse 30%)
m³/h
880
Air flow range
m
2,5
Power consumption
W
93
Current consumption
A
0,41
Acoustic pressure level at a distance of 3 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
49
Acoustic pressure level at a distance of 5 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
48
Acoustic power level according to ISO 27327-2
dB(A)
64
Fan data at 1st (min) speed
Air flow
m³/h
1150
Air flow with filter (Coarse 30%)
m³/h
720
Air flow range
m
1,8
Power consumption
W
78
Current consumption
A
0,35
Acoustic pressure level at a distance of 3 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
45
Acoustic pressure level at a distance of 5 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
44
Acoustic power level according to ISO 27327-2
dB(A)
59
Installation data
Power supply
V/Hz
1N ~ 230/50
IP protection class
20
Installation
Horizontal / vertical
Max. heating water temperature
°C
110
Max. operating pressure
MPa
1,6
Hydraulic connection
Ø "
½
Max. mounting height
m
3,5
Other data
Color
White
Dimensions
Length
mm
1500
Depth
mm
399
Height
mm
189
Weight without water
kg
22,7
Weight of unit filled with water
kg
24,4

Dimensions

Model: SLIM W-150 2R WHITE

Heating capacity tables

SLIM W-150 2R WHITE airflow on 3 speed = 1830 m³/h
Tp1
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
 
0
5
10
15
20
Tw1/Tw2 = 110/90°C
35,3
1571
23,9
57,0
33,6
1495
21,8
59,5
31,9
1420
19,9
61,5
30,2
1345
18,0
63,5
28,5
1271
16,2
65,5
 
0
5
10
15
20
Tw1/Tw2 = 90/70°C
27,7
1221
15,9
45,0
25,9
1145
14,1
47,0
24,2
1069
12,5
49,0
22,5
993
10,9
51,0
20,8
917
9,5
53,0
 
0
5
10
15
20
Tw1/Tw2 = 80/60°C
23,9
1049
12,4
39,0
22,1
972
10,8
41,0
20,4
896
9,3
43,0
18,7
820
8,0
45,0
16,9
743
6,7
47,0
 
0
5
10
15
20
Tw1/Tw2 = 70/50°C
20,1
877
9,3
32,5
18,3
801
7,9
34,5
16,6
724
6,6
36,5
14,8
647
5,4
39,0
13,0
569
4,3
41,0
 
0
5
10
15
20
Tw1/Tw2 = 60/40°C
16,2
707
6,5
26,5
14,4
629
5,3
28,5
12,7
552
4,2
30,5
10,9
473
3,2
32,5
9,0
393
2,3
34,5
 
0
5
10
15
20
Tw1/Tw2 = 50/40°C
15,4
1335
20,9
25,0
13,6
1182
16,8
27,0
11,8
1028
13,1
29,0
10,0
873
9,8
31,0
8,2
717
6,9
33,0
SLIM W-150 2R WHITE airflow on 2 speed = 1310 m³/h
Tp1
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
 
0
5
10
15
20
Tw1/Tw2 = 110/90°C
28,1
1250
15,7
63,5
26,7
1189
14,4
65,0
25,4
1130
13,1
67,0
24,0
1070
11,9
68,5
22,7
1011
10,7
70,5
 
0
5
10
15
20
Tw1/Tw2 = 90/70°C
22,0
972
10,5
50,0
20,7
911
9,3
51,5
19,3
851
8,3
53,5
17,9
791
7,2
55,0
16,6
731
6,3
57,0
 
0
5
10
15
20
Tw1/Tw2 = 80/60°C
19,0
835
8,2
43,0
17,6
774
7,2
45,0
16,2
714
6,2
46,5
14,9
653
5,3
48,5
13,5
592
4,4
50,0
 
0
5
10
15
20
Tw1/Tw2 = 70/50°C
16,0
699
6,2
36,0
14,6
638
5,3
38,0
13,2
577
4,4
39,5
11,8
515
3,6
41,5
10,4
454
2,9
43,0
 
0
5
10
15
20
Tw1/Tw2 = 60/40°C
12,9
563
4,4
29,5
11,5
502
3,6
31,0
10,1
440
2,8
33,0
8,6
377
2,1
34,5
7,2
313
1,5
36,0
 
0
5
10
15
20
Tw1/Tw2 = 50/40°C
12,2
1062
13,9
27,5
10,8
941
11,1
29,5
9,4
819
8,7
31,0
8,0
695
6,5
33,0
6,6
571
4,6
34,5
SLIM W-150 2R WHITE airflow on 1 speed = 1150 m³/h
Tp1
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
 
0
5
10
15
20
Tw1/Tw2 = 110/90°C
25,5
1138
13,3
66,0
24,3
1083
12,1
67,5
23,1
1028
11,0
69,0
21,9
974
10,0
71,0
20,7
921
9,0
72,5
 
0
5
10
15
20
Tw1/Tw2 = 90/70°C
20,1
885
8,9
52,0
18,8
830
7,9
53,5
17,6
775
7,0
55,0
16,3
720
6,1
56,5
15,1
666
5,3
58,5
 
0
5
10
15
20
Tw1/Tw2 = 80/60°C
17,3
761
6,9
44,5
16,1
705
6,1
46,5
14,8
650
5,2
48,0
13,5
595
4,5
49,5
12,3
539
3,8
51,0
 
0
5
10
15
20
Tw1/Tw2 = 70/50°C
14,6
637
5,2
37,5
13,3
581
4,4
39,5
12,0
526
3,7
41,0
10,7
470
3,0
42,5
9,4
413
2,4
44,0
 
0
5
10
15
20
Tw1/Tw2 = 60/40°C
11,8
513
3,7
30,5
10,5
457
3,0
32,0
9,2
401
2,4
33,5
7,9
343
1,8
35,0
6,5
285
1,3
36,5
 
0
5
10
15
20
Tw1/Tw2 = 50/40°C
11,1
968
11,7
29,0
9,9
857
9,4
30,5
8,6
746
7,4
32,0
7,3
633
5,5
33,5
6,0
520
3,9
35,5
  • PT - heating capacity
  • Tp1 - air temperature at the unit inlet
  • Tp2 - air temperature at the unit outlet
  • Tw1 - heating medium temperature at the heat exchanger inlet
  • Tw2 - heating medium temperature at the heat exchanger outlet
  • Qw - heating medium flow rate in heat exchanger
  • Δpw - heating medium pressure drop in heat exchanger

If you want to calculate heating capacity at different parameters you can do this at manufacturer website.