Water air curtain, horizontal and vertical mounting, EPP casing, max. mounting height 4 m, protection class IP21, heating capacity: from 9.9 kW (50/40°C) to 27.4 kW (90/70°C), one row copper heat exchanger with aluminum plates, air flow: three speeds 3000/4100/5100 m³/h, fan power 440 W, length 2 m, 3 year WARRANTY
Interested in this product? Contact us:

Arvydas Palivonas

LT, RU, EN
+370 601 74426

Sales representative for Vilnius, Ukmergė, Utena, Kaišiadorys and Varėna regions Get Offer

Andrius Lekarevičius

LT, RU, EN
+370 606 11865

Sales representative for Kaunas, Panevėžys, Šiauliai, Telšiai, Klaipėda, Tauragė, Marijampolė and Alytus districts Get Offer
Click on the Model for technical data, dimensions, accessories
ELiS T-W - horizontal and vertical mounting, EPP casing, max. mounting height 4 m, protection class IP21
ELiS T-W-100 Heating capacity: from 4.6 kW (50/40°C) to 11.1 kW (90/70°C), one row copper heat exchanger with aluminum plates, air flow: three speeds 1900/2100/2300 m³/h, fan power 380 W, length 1 m, 3 year WARRANTY
ELiS T-W-100
Heating capacity: from 4.6 kW (50/40°C) to 11.1 kW (90/70°C), one row copper heat exchanger with aluminum plates, air flow: three speeds 1900/2100/2300 m³/h, fan power 380 W, length 1 m, 3 year WARRANTY
ELiS T-W-150 Heating capacity: from 8.5 kW (50/40°C) to 20.2 kW (90/70°C), one row copper heat exchanger with aluminum plates, air flow: three speeds 3100/3500/3900 m³/h, fan power 400 W, length 1.5 m, 3 year WARRANTY
ELiS T-W-150
Heating capacity: from 8.5 kW (50/40°C) to 20.2 kW (90/70°C), one row copper heat exchanger with aluminum plates, air flow: three speeds 3100/3500/3900 m³/h, fan power 400 W, length 1.5 m, 3 year WARRANTY
ELiS T-W-200 Heating capacity: from 9.9 kW (50/40°C) to 27.4 kW (90/70°C), one row copper heat exchanger with aluminum plates, air flow: three speeds 3000/4100/5100 m³/h, fan power 440 W, length 2 m, 3 year WARRANTY
ELiS T-W-200
Heating capacity: from 9.9 kW (50/40°C) to 27.4 kW (90/70°C), one row copper heat exchanger with aluminum plates, air flow: three speeds 3000/4100/5100 m³/h, fan power 440 W, length 2 m, 3 year WARRANTY
ELiS T-W-100 2R Heating capacity: from 9.1 kW (50/40°C) to 21.5 kW (90/70°C), two rows copper heat exchanger with aluminum plates, air flow: three speeds 1700/1900/2100 m³/h, fan power 380 W, length 1 m, 3 year WARRANTY
ELiS T-W-100 2R
Heating capacity: from 9.1 kW (50/40°C) to 21.5 kW (90/70°C), two rows copper heat exchanger with aluminum plates, air flow: three speeds 1700/1900/2100 m³/h, fan power 380 W, length 1 m, 3 year WARRANTY
ELiS T-W-150 2R Heating capacity: from 16.1 kW (50/40°C) to 38.4 kW (90/70°C), two rows copper heat exchanger with aluminum plates, air flow: three speeds 2900/3300/3700 m³/h, fan power 400 W, length 1.5 m, 3 year WARRANTY
ELiS T-W-150 2R
Heating capacity: from 16.1 kW (50/40°C) to 38.4 kW (90/70°C), two rows copper heat exchanger with aluminum plates, air flow: three speeds 2900/3300/3700 m³/h, fan power 400 W, length 1.5 m, 3 year WARRANTY
ELiS T-W-200 2R Heating capacity: from 16.8 kW (50/40°C) to 49.3 kW (90/70°C), two rows copper heat exchanger with aluminum plates, air flow: three speeds 2800/3800/4900 m³/h, fan power 440 W, length 2 m, 3 year WARRANTY
ELiS T-W-200 2R
Heating capacity: from 16.8 kW (50/40°C) to 49.3 kW (90/70°C), two rows copper heat exchanger with aluminum plates, air flow: three speeds 2800/3800/4900 m³/h, fan power 440 W, length 2 m, 3 year WARRANTY
Model: ELiS T-W-200
General data
Heating capacity at 90/70°C water and 10°C air temperature, fan at max speed
kW
27,4
Heating capacity at 50/40°C water and 10°C air temperature, fan at min speed
kW
9,9
Air flow range (measured verticaly at 2 m/s speed limit)
m
4
Air temperature rise (ΔT) at 90/70°C water and at 10°C air temperature
°C
16,0
Max. air flow
m³/h
5100
Fan data
Power supply
V/Hz
1N ~ 230/50
IP / Insulation class
21 / F
Steps
3
Fan data at 3rd (max) speed
Air flow
m³/h
5100
Power consumption
W
440
Current consumption
A
2,0
Acoustic pressure level at a distance of 5 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
62
Fan data at 2nd (mid) speed
Air flow
m³/h
4100
Power consumption
W
380
Current consumption
A
1,7
Acoustic pressure level at a distance of 5 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
60
Fan data at 1st (min) speed
Air flow
m³/h
3000
Power consumption
W
0,33
Current consumption
A
1,5
Acoustic pressure level at a distance of 5 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
58
Installation data
Installation
Horizontal / vertical
Max. heating water temperature
°C
95
Max. operating pressure
MPa
1,6
Hydraulic connection
Ø "
½
Other data
Heat exchanger
Copper with aluminum plates, one row
Casing
EPP + plastic + steel sheet
Color
Grey / graphite (RAL 9007)
Dimensions
Length
mm
2020
Depth
mm
377
Height
mm
253
Weight
kg
34,3
Weight of unit filled with water
kg
35,9

Dimensions

Model: ELiS T-W-200

Heating capacity tables

ELiS T-W-200 airflow on 3 speed = 5100 m³/h
Tp1
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
 
0
5
10
15
20
Tw1/Tw2 = 90/70°C
31,4
1387
14,5
18,0
29,4
1299
12,8
22,0
27,4
1211
11,3
26,0
25,4
1122
9,8
29,0
23,4
1033
8,4
33,0
 
0
5
10
15
20
Tw1/Tw2 = 80/60°C
26,9
1183
11,1
15,0
24,9
1095
9,6
19,5
22,9
1005
8,2
23,0
20,8
916
7,0
27,0
18,8
826
5,8
30,5
 
0
5
10
15
20
Tw1/Tw2 = 70/50°C
22,4
980
8,1
12,5
20,6
891
6,8
16,0
18,3
801
5,6
20,5
16,2
710
4,5
24,0
14,4
619
3,5
27,5
 
0
5
10
15
20
Tw1/Tw2 = 70/40°C
18,3
533
2,8
10,5
16,2
472
2,2
14,0
14,1
410
1,7
18,0
11,9
347
1,3
21,5
9,7
281
0,9
25,0
 
0
5
10
15
20
Tw1/Tw2 = 60/40°C
17,8
776
5,5
10,0
15,7
686
4,4
14,0
13,6
595
3,4
18,0
11,5
502
2,5
21,5
9,4
408
1,7
25,0
 
0
5
10
15
20
Tw1/Tw2 = 50/40°C
17,4
1513
18,8
10,0
15,3
1334
15,0
14,0
13,3
1153
11,5
17,5
11,2
971
8,4
21,0
9,0
786
5,8
24,5
ELiS T-W-200 airflow on 2 speed = 4100 m³/h
Tp1
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
 
0
5
10
15
20
Tw1/Tw2 = 90/70°C
28,0
1234
11,7
20,0
26,2
1155
10,3
24,0
24,4
1077
9,1
27,0
22,6
998
7,9
31,0
20,8
919
6,8
35,0
 
0
5
10
15
20
Tw1/Tw2 = 80/60°C
24,0
1052
9,0
17,0
22,2
974
7,8
21,0
20,4
895
6,7
24,5
18,6
815
5,6
28,0
16,7
735
4,7
32,0
 
0
5
10
15
20
Tw1/Tw2 = 70/50°C
19,9
872
6,6
14,5
18,1
792
5,5
18,0
16,3
713
4,6
21,5
14,5
632
3,7
25,0
12,6
551
2,9
28,5
 
0
5
10
15
20
Tw1/Tw2 = 70/40°C
16,3
474
2,2
11,5
14,4
420
1,8
15,0
12,5
365
1,4
19,0
10,6
308
1,0
22,5
8,6
249
0,7
26,0
 
0
5
10
15
20
Tw1/Tw2 = 60/40°C
15,8
690
4,5
11,5
14,0
610
3,6
15,0
12,1
529
2,7
19,0
10,2
447
2,0
22,5
8,3
362
1,4
25,5
 
0
5
10
15
20
Tw1/Tw2 = 50/40°C
15,5
1345
15,2
11,0
13,6
1186
12,0
14,5
11,8
1025
9,3
18,5
9,9
864
6,8
22,0
8,0
700
4,7
25,5
ELiS T-W-200 airflow on 1 speed = 3000 m³/h
Tp1
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
 
0
5
10
15
20
Tw1/Tw2 = 90/70°C
23,5
1037
8,5
23,5
22,0
972
7,5
27,0
20,5
906
6,6
30,5
19,0
840
5,8
33,5
17,5
774
5,0
37,0
 
0
5
10
15
20
Tw1/Tw2 = 80/60°C
20,1
885
6,5
20,0
18,6
819
5,7
23,5
17,1
753
4,9
27,0
15,6
686
4,1
30,5
14,1
619
3,4
34,0
 
0
5
10
15
20
Tw1/Tw2 = 70/50°C
16,8
733
4,8
16,5
15,2
667
4,0
20,0
13,7
600
3,3
23,5
12,2
532
2,7
27,0
10,6
464
2,1
30,5
 
0
5
10
15
20
Tw1/Tw2 = 70/40°C
13,7
399
1,6
13,5
12,1
353
1,3
17,0
10,5
306
1,0
20,5
8,9
258
0,8
24,0
7,1
207
0,5
27,0
 
0
5
10
15
20
Tw1/Tw2 = 60/40°C
13,3
581
3,3
13,5
11,8
513
2,6
16,5
10,2
445
2,0
20,0
8,6
375
1,5
23,5
7,0
304
1,0
27,0
 
0
5
10
15
20
Tw1/Tw2 = 50/40°C
13,0
1130
11,1
13,0
11,5
996
8,8
16,5
9,9
862
6,8
20,0
8,3
726
5,0
23,5
6,8
589
3,4
26,5
  • PT - heating capacity
  • Tp1 - air temperature at the unit inlet
  • Tp2 - air temperature at the unit outlet
  • Tw1 - heating medium temperature at the heat exchanger inlet
  • Tw2 - heating medium temperature at the heat exchanger outlet
  • Qw - heating medium flow rate in heat exchanger
  • Δpw - heating medium pressure drop in heat exchanger

If you want to calculate heating capacity at different parameters you can do this at manufacturer website.

High productivity and successful integration of new materials allowed the company FLOWAIR to reduce the price, but not the quality of its air curtain ELiS T. The casing from EPP (expanded polypropylene), which was a matter of great interest at the beginning, has become an integral part of the air curtains ELiS T. Thanks to the material, the casing has become lighter, however, remains strong and elastic at the same time. The grey-coloured air curtain ELiS T in the modern design is a multi-purpose unit – it can be mounted both horizontally over doorways and vertically along the side of a doorway. The stronger air blow, which can be adjusted with a three-speed controller makes it possible to mount the air curtain at the height of as many as 4 meters (see Fig. 1). The air from the intake of the unit is preheated by a hot water heat exchanger; meanwhile, the flow fans blow the preheated air out (see Fig. 2). The air curtain ELiS T has water connections on the top and on the left; the heat exchanger has an air relief valve on the right. This allows vertical installation of the air curtain both on the left and right side of a doorway.

ELiS T air curtains principle of operation
Fig. 2: Principle of operation of an air curtain ELiS T: (1) the air from the intake is preheated by a hot water heat exchanger inside, and (2) the air is blown downwards with a flow fan.

Air curtains ELiS T are available in three sizes: 1 m, 1.5 m and 2 m long. Furthermore, the curtains can be mounted in a row to create a screen of required width (2.5 m, 3 m, 3.5 m, etc.). In order the air curtain turned on automatically each time the door is opened, and turned off automatically upon the door closed, a mechanical door contact can be involved. If you want the unit to respond to the signal from a magnetic door contact, the DRV control system module is needed (see Fig. 3). The module can be ordered as an option. DRV is an advanced control system which can be connected to BMS (building management system). To disconnect the heating for the air curtain, a servo valve is needed which stops the supply of hot water to the heat exchanger. The valve is controlled with a thermostat or magnetic door sensor.

Enhanced air flow, decreased weight, attractive design and an even better price make the air curtain an excellent choice for commercial enterprises, public institutions and other places, where an effective air screen is needed to protect heated or cooled premises against cold or hot air forcing from the outside to the inside through a door, which is opened on a constant basis.

DRV control system module
Fig. 3: DRV control system module

The advantages of a universal water air curtain ELiS T with EPP casing:

  • Stronger air flow at a better price!
  • Universal air curtain – for installation both horizontally and vertically.
  • EPP and steel casing. The framework is from galvanized steel.
  • An air screen protects against: winter cold, summer heat, smoke, bad smells, insects, dust.
  • A wide selection of models: the air curtains are available in three sizes; they can be mounted in a row to obtain the required length.
  • Only premium quality components: cross flow fans, high quality copper heat exchangers with aluminum plate-fins, a casing from steel and expanded polypropylene.
  • A wide scope of application.
  • Quality guarantee – European product with technical properties meeting the declared values, CE certified.
  • Extensive application: shops, banks, bookstores, pharmacies, hotels, restaurants, cafes, pubs, administrative offices, vestibules and other objects.
  • DRV control system module as an option. The DRV control system can be connected to BMS. The DRV control system provides the possibility to operate up to 5 air curtains with a single control panel, also engage a magnetic door sensor.

ELiS T EPP installation
Fig. 1: Installation of air curtains ELiS T

ELiS T EPP air curtains
Manuals 2.1 MB
Declarations of conformity 386 KB
Brochures 12.9 MB
Catalogue 1 MB
Hygienic certificate 557 KB
AutoCAD drawings 1.3 MB
BIM objects 9.4 MB
TS controller for equipment with 3-speed fans
Manuals 187 KB
Declarations of conformity 211 KB
HMI programable controller for equipment with 3-speed fans
Manuals 811 KB
Declarations of conformity 1.5 MB
MODBUS protocol for connection to BMS 148 KB
T-box controller
Manuals 22.7 MB
Declarations of conformity 643 KB
MODBUS protocol for connection to BMS 1.9 MB
T-box Zone controller
Manuals 7.4 MB
Declarations of conformity 643 KB
MODBUS protocol for connection to BMS 1.7 MB
DRV ELiS control module for 3-speed air curtains
Manuals 1.5 MB
RX control signal splitter for equipment with 3-speed fans
Manuals 2 MB
Declarations of conformity 210 KB
DCet magnetic door switch with relay
Manuals 978 KB