Water air curtain, horizontal and vertical mounting, 3 step fan, protection class IP20, mounting height up to 3.5 m, built in control system (motion sensor), very thin - only 189 mm in height, can be connected to BMS, heating capacity: from 7.5 kW (50/40°C) to 20.5 kW (90/70°C), air flow 1760/2260/2910 m³/h, fan power 115/150/230 W, sound pressure level 37/45/58 dB(A), length 2 m, weight 26.9 kg, black color, 2 year WARRANTY
Interested in this product? Contact us:

Arvydas Palivonas

LT, RU, EN
+370 601 74426

Sales representative for Vilnius, Ukmergė, Utena, Kaišiadorys and Varėna regions Get Offer

Andrius Lekarevičius

LT, RU, EN
+370 606 11865

Sales representative for Kaunas, Panevėžys, Šiauliai, Telšiai, Klaipėda, Tauragė, Marijampolė and Alytus districts Get Offer
Model: SLIM W-200/AS BLACK
General data
Heating capacity at 90/70°C water and 10°C air temperature, fan at max speed
kW
20,5
Heating capacity at 50/40°C water and 10°C air temperature, fan at min speed
kW
7,5
Air flow range
m
3,5
Max. air flow
m³/h
2910
Fan data
Steps
3
Fan data at 3rd (max) speed
Air flow
m³/h
2910
Air flow with filter (Coarse 30%)
m³/h
1900
Air flow range
m
3,5
Power consumption
W
230
Current consumption
A
1,0
Acoustic pressure level at a distance of 3 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
59
Acoustic pressure level at a distance of 5 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
58
Acoustic power level according to ISO 27327-2
dB(A)
74
Fan data at 2nd (mid) speed
Air flow
m³/h
2260
Air flow with filter (Coarse 30%)
m³/h
1600
Air flow range
m
2,8
Power consumption
W
150
Current consumption
A
0,6
Acoustic pressure level at a distance of 3 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
46
Acoustic pressure level at a distance of 5 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
45
Acoustic power level according to ISO 27327-2
dB(A)
61
Fan data at 1st (min) speed
Air flow
m³/h
1760
Air flow with filter (Coarse 30%)
m³/h
1350
Air flow range
m
2,1
Power consumption
W
115
Current consumption
A
0,5
Acoustic pressure level at a distance of 3 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
38
Acoustic pressure level at a distance of 5 m from the unit, in the 1500 m³ room of medium capabillity of sound absorption
dB(A)
37
Acoustic power level according to ISO 27327-2
dB(A)
53
Installation data
Power supply
V/Hz
1N ~ 230/50
IP protection class
20
Installation
Horizontal / vertical
Max. heating water temperature
°C
110
Max. operating pressure
MPa
1,6
Hydraulic connection
Ø "
½
Max. mounting height
m
3,5
Other data
Color
Black
Dimensions
Length
mm
2000
Depth
mm
399
Height
mm
189
Weight without water
kg
26,9
Weight of unit filled with water
kg
28,1

Dimensions

Model: SLIM W-200/AS BLACK

Heating capacity tables

SLIM W-200/AS BLACK airflow on 3 speed = 2910 m³/h
Tp1
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
 
0
5
10
15
20
Tw1/Tw2 = 110/90°C
29,6
1318
64,8
30,0
28,2
1256
59,3
34,0
26,8
1195
54,0
37,0
25,4
1133
49,0
40,5
24,1
1071
44,2
44,0
 
0
5
10
15
20
Tw1/Tw2 = 90/70°C
23,3
1028
43,1
24,0
21,9
965
38,4
27,5
20,5
902
34,0
31,0
19,0
840
29,8
34,5
17,6
776
25,9
37,5
 
0
5
10
15
20
Tw1/Tw2 = 80/60°C
20,1
884
33,7
20,5
18,7
822
29,5
24,0
17,3
758
25,5
27,5
15,8
695
21,8
31,0
14,4
631
18,3
34,5
 
0
5
10
15
20
Tw1/Tw2 = 70/50°C
17,0
742
25,4
17,5
15,5
679
21,6
21,0
14,1
615
18,1
24,5
12,6
551
14,8
28,0
11,1
486
11,9
31,0
 
0
5
10
15
20
Tw1/Tw2 = 60/40°C
13,8
601
18,0
14,0
12,3
537
14,7
17,5
10,8
472
11,7
21,0
9,3
407
9,0
24,5
7,8
340
6,5
28,0
 
0
5
10
15
20
Tw1/Tw2 = 50/40°C
13,0
1128
57,1
13,5
11,5
1001
45,9
17,0
10,0
873
35,9
20,5
8,5
743
26,9
23,5
7,0
612
19,0
27,0
SLIM W-200/AS BLACK airflow on 2 speed = 2260 m³/h
Tp1
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
 
0
5
10
15
20
Tw1/Tw2 = 110/90°C
25,6
1140
49,6
33,5
24,4
1087
45,4
37,0
23,2
1033
41,4
40,5
22,0
980
37,6
43,5
20,8
927
33,9
47,0
 
0
5
10
15
20
Tw1/Tw2 = 90/70°C
20,1
889
33,1
26,5
18,9
835
29,5
30,0
17,7
781
26,1
33,0
16,5
726
22,9
36,5
15,2
672
19,9
39,5
 
0
5
10
15
20
Tw1/Tw2 = 80/60°C
17,4
765
25,9
23,0
16,2
711
22,7
26,0
14,9
656
19,6
29,5
13,7
601
16,8
33,0
12,4
546
14,1
36,0
 
0
5
10
15
20
Tw1/Tw2 = 70/50°C
14,7
642
19,5
19,5
13,4
587
16,6
22,5
12,2
532
14,0
26,0
10,9
477
11,5
29,0
9,6
421
9,2
32,5
 
0
5
10
15
20
Tw1/Tw2 = 60/40°C
11,9
520
13,9
15,5
10,7
464
11,4
19,0
9,4
409
9,0
22,5
8,1
352
6,9
25,5
6,8
294
5,1
29,0
 
0
5
10
15
20
Tw1/Tw2 = 50/40°C
11,2
975
43,8
15,0
10,0
865
35,3
18,0
8,7
755
27,6
21,5
7,4
643
20,7
24,5
6,1
530
14,7
28,0
SLIM W-200/AS BLACK airflow on 1 speed = 1760 m³/h
Tp1
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
PT
Qw
∆pw
Tp2
kW
l/h
kPa
°C
 
0
5
10
15
20
Tw1/Tw2 = 110/90°C
22,1
983
37,8
37,0
21,0
937
34,6
40,5
20,0
891
31,6
43,5
19,0
845
28,6
46,5
17,9
799
25,9
49,5
 
0
5
10
15
20
Tw1/Tw2 = 90/70°C
17,4
766
25,3
29,5
16,3
720
22,5
32,5
15,3
673
20,0
35,5
14,2
626
17,5
38,5
13,1
579
15,2
42,0
 
0
5
10
15
20
Tw1/Tw2 = 80/60°C
15,0
660
19,8
25,5
14,0
613
17,4
28,5
12,9
566
15,0
31,5
11,8
518
12,9
34,5
10,7
471
10,8
38,0
 
0
5
10
15
20
Tw1/Tw2 = 70/50°C
12,7
554
15,0
21,5
11,6
507
12,8
24,5
10,5
459
10,7
27,5
9,4
411
8,8
30,5
8,3
363
7,0
34,0
 
0
5
10
15
20
Tw1/Tw2 = 60/40°C
10,3
448
10,7
17,5
9,2
401
8,7
20,5
8,1
352
7,0
23,5
7,0
304
5,4
26,5
5,8
254
3,9
29,5
 
0
5
10
15
20
Tw1/Tw2 = 50/40°C
9,7
840
33,5
16,5
8,6
746
27,0
19,5
7,5
650
21,2
22,5
6,4
554
15,9
25,5
5,3
457
11,3
29,0
  • PT - heating capacity
  • Tp1 - air temperature at the unit inlet
  • Tp2 - air temperature at the unit outlet
  • Tw1 - heating medium temperature at the heat exchanger inlet
  • Tw2 - heating medium temperature at the heat exchanger outlet
  • Qw - heating medium flow rate in heat exchanger
  • Δpw - heating medium pressure drop in heat exchanger

If you want to calculate heating capacity at different parameters you can do this at manufacturer website.