Gas heater, condensing, with fixed airflow centrifugal AC fan for ducts system, pre-mix burner, heat output modulation from 100% to 30%, can be connected to BMS via Modbus RTU protocol, 19.5-56.6 kW modulating heat output, air flow 5400 m³/h at 120 Pa, electrical power absorbtion 1.50 kW, max. gas (G20) consumption 6.14 m³/h, weight 109 kg, 2 year WARRANTY
Interested in this product? Contact us:

Arvydas Palivonas

LT, RU, EN
+370 601 74426

Sales representative for Vilnius, Ukmergė, Utena, Kaišiadorys and Varėna regions Get Offer

Andrius Lekarevičius

LT, RU, EN
+370 606 11865

Sales representative for Kaunas, Panevėžys, Šiauliai, Telšiai, Klaipėda, Tauragė, Marijampolė and Alytus districts Get Offer
Click on the Model for technical data, dimensions, accessories
NEXT-G C series - condensing, with fixed airflow centrifugal AC fan for ducts system, pre-mix burner, heat output modulation from 100% to 30%, can be connected to BMS via Modbus RTU protocol
NEXT-G 30 C 9.9-27.4 kW modulating heat output, air flow 2500 m³/h at 140 Pa, electrical power absorbtion 0.65 kW, max. gas (G20) consumption 2.97 m³/h, weight 78 kg, 2 year WARRANTY
NEXT-G 30 C
9.9-27.4 kW modulating heat output, air flow 2500 m³/h at 140 Pa, electrical power absorbtion 0.65 kW, max. gas (G20) consumption 2.97 m³/h, weight 78 kg, 2 year WARRANTY
NEXT-G 60 C 19.5-56.6 kW modulating heat output, air flow 5400 m³/h at 120 Pa, electrical power absorbtion 1.50 kW, max. gas (G20) consumption 6.14 m³/h, weight 109 kg, 2 year WARRANTY
NEXT-G 60 C
19.5-56.6 kW modulating heat output, air flow 5400 m³/h at 120 Pa, electrical power absorbtion 1.50 kW, max. gas (G20) consumption 6.14 m³/h, weight 109 kg, 2 year WARRANTY
Model: NEXT-G 60 C
General data
Nominal heat output (min - max)
kW
18,5 - 58,0
Delivered thermal power (min. - max.)
kW
19,5 - 56,6
Efficiency (at min - max heating power)
%
105,2 - 97,5
Natural gas (G20) consumption
m³/h
6,14
LPG (G30) consumption
kg/h
4,54
Air flow at maximum allowed static pressure
m³/h
5400
Air flow at free blowing
m³/h
6500
Fan data
Static pressure
Pa
120
Minimal allowed static pressure drop on ducts
Pa
0
Installation data
Power supply
V/ph
230V 1N - 50 Hz
Power electric consumption
W
1500
IP protection class
20
Gas connection
Ø "
M 3/4
Operating temperature range
°C
0 / +40
Installation type
B23, B23P, C13, C33, C53, C63
Exhaust air flue diameter
mm Ø
80
Air Inlet flue diameter
mm Ø
80
Dimensions
Width
mm
969
Depth
mm
777
Height
mm
1138
Weight
kg
109

Dimensions

Model: NEXT-G 60 C
NEXT-G condensing and modulating gas fired unit heaters
Manuals 15.6 MB
Catalogue 1.6 MB
MODBUS protocol for connection to BMS 155 KB
Re-Mote digital control panel
Manuals 3.5 MB